T-D10
Electrical Winding Insulation, Electrical Base
Red
Polyolefin, silicone rubber
10KV~20KV
Organic Insulation
Organic Insulating Material
ISO9001, SGS
LV Bushing Cover
United Electric
United Electric
Carton Box
P. R. China
8547200000
Product Description
Distribution transformer low voltage bushing protection cover


Substation equipment is vulnerable to flashovers caused by accidental bridging of phases, or phase to earth. Usually made by birds, animals, vegetation or airborne debris, flashovers can be very expensive in terms of damage to equipment, reduced reliability and in some cases even electrocution of protected species.
Almost any event of this nature can be prevented by insulating the strategically vulnerable bare metalwork with a combination of the isolation protection covers.
Substation buhsing isolation protection covers made by United Electric are designed to protect the electrical connections from animals and corrosion and unexpected touch etc., to make electricity using in saver way.
Feature
• Easy and simple installation, tool free application, long service life.
• Covers are held in place with UV-stabilized plastic nuts and bolts, be easily removed for maintenance.
• Excellent UV and weather resistance, anti-tracking and wear resistance.
• Excellent pollution resistance and hydrophobic performance.
• Standard color: Red. Other colors are available upon to request.
Material test data
Property | Test method | Typical data |
Tensile strength | ASTM D 2671 | ≥12MPa |
Tensile strength after aging | ASTM D 2671 (120°C /168hrs) | ≥10MPa |
Elongation at break | ASTM D 2671 | ≥400% |
Elongation at break after aging | ASTM D 2671 (120°C /168hrs) | ≥300% |
Dielectric strength | IEC 243 | ≥12kV/mm |
Volume resistance | IEC 93 | ≥1012Ω.cm |
Flammability | IEC 60684-2 Method C | 60sec max. |
Low temperature flexibility | ASTM D 2671 | -40°C, 4hrs, no cracking |
Water absirption | ISO 62 (23°C /14days) | <0.5% |
Electrical test data
Test item | Test method | Test result |
Fault connection of other articles | Applied voltage 21kV loading time 1min leakage current ≤2 mA | Pass |
Leakage current | ≤2 mA | Pass |
Material test data
Property | Test method | Typical data |
Tensile strength | ASTM D2671 | ≥12MPa |
Elongation at break | ASTM D2671 | ≥200% |
Dielectric strength | IEC 60243 | ≥10kV/mm (3mm) |
Volume resistance | IEC 93 | ≥1014Ω·cm |
Water absorption | ISO 62 | ≤0.5% |
Heat shock at 225°C / 4hrs | ASTM D2671 | No cracking, dropping |
Density | ASTM D792 | 1.1~1.3g/cm³ |