Product Description
Medium Voltage Pre-molded Indoor Termination for up to 42kV for XLPE Cable
• One-piece design with integrated stress cone.
• Quick and easy push-on installation.
• Long time storage, quick delivery.
• High quality silicone rubber, reliable insulation.
• Wide usage.
• Suitable for XLPE cable up to 42kV.

Features
• Power Cable Termination Voltage Class(kV): ≤ 42
• Cable Shield Style: Copper wire, copper tape
• Number of Cores: 1, 3
• Application Type: Indoor
• Industry Standards: Design Specification GB/T 12706.4, IEC 60502-4

1.cable lug
2.pre-molded indoor termination
3.semi-conductive tape
4.copper tape screen
5.heat shrinkable protective tube
6.heat shrinkable breakout
7.copper braid
2.pre-molded indoor termination
3.semi-conductive tape
4.copper tape screen
5.heat shrinkable protective tube
6.heat shrinkable breakout
7.copper braid
Specification
RXS/GCA HN15 | RXS/GCA HN20 | RXS/GCA HN35 | |||
Conductor size (mm2) | Core insulation outer dia. min/ max(mm) | Conductor size (mm2) | Core insulation outer dia. min/ max(mm) | Conductor size (mm2) | Core insulation outer dia. min/ max(mm) |
25 | 15.0-41.0 | 35-50 | 19.0-41.0 | 50-70 | 30.0-61.0 |
35-50 | 70-95 | 95-120 | |||
70-95 | 120-150 | 150-185 | |||
120-150 | 185 | 240 | |||
185-240 | 240 | 300 | |||
300 | 300 | 400 | |||
400 | 400 | 500 | |||
500 | 500 | 630 | |||
630 |
Technical Data
Test item | 8.7/15(17.5)kV | 12/20(24)kV | 26/35(42)kV |
A.C. voltage withstand test | No flashover, no breakdown at 39kV for 5min. | No flashover, no breakdown at 54kV for 5min. | No flashover, no breakdown at 117kV for 5min. |
Partial discharge test | 15kV, <2pC | 20kV, <2pC | 45kV, <2pC |
Heating cycles voltage test | 63 cycles at 95-100°C, 23kV | 63 cycles at 95-100°C, 30kV | 63 cycles at 95-100°C, 65kV |
Impulse voltage withstand test at 95- 100°C | No flashover, no breakdown at 10 positive and 10 negative impulses at 95kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 125kV | No flashover, no breakdown at 10 positive and 10 negative impulses at 200kV |
Thermal short-circuit test | No deformation or welding at 31.0kA,2.02s and 31.1kA,2.02s | No deformation or welding at 31.0kA,2.03s and 31.0kA,2.02s | No deformation or welding at 31.0kA,2.03s and 30.8kA,2.04s |
Dynamic short-circuit test | No deformation or welding at 112.3kA,60ms | No deformation or welding at 111.3kA,60ms | No deformation or welding at 112.2kA,60ms |
15min, A.C. voltage withstanding test | 23kV, 15min. no flashover, no breakdown | 30kV, 15min. no flashover, no breakdown | 65kV, 15min.no flashover, no breakdown |