XGN15-12/630-25
Sf6 Gas Insulated Switch Protection System
Combination Can Also Be Used Independently
Sf6 Insulated
Remote Control Microcomputer Protection
Automatic Control, Protection, Monitoring, Measurement
RoHS, CCC, ISO: 9001, CE, Custimozed
New
Customized
Galvanized Steel Plate
Earthing, Fuse, Microcomputer(for 35kv)
Sf6 Load Break Switch
Manual /Mortor Mechanism
12kv 24kv 35kv 40.5kv
630A
Can Instead of Sm6 Use
Wooden Pallet
Yueqing, Zhejiang, China
Sf6 Load Break Switch
25ka
Switching Mode
MINGZHE
Wooden Pallet
600x900x2000
China
8537209000
Product Description
1.Brief Introduction
XGN15-12(L)/T630-25 0r XGN15-12(L . R)/T100-31.5 Cubicle fixed AC metal enclosed switchgear is mainly used for looped network power supply or biradial power supply of electric power system with 3-phase ,AC 50Hz and rated voltage 10KV. It also can be used for terminal power supply as the control device of electric energy and protection device of utilization equipment. More over, it also can be suitable for this switchgearto be installed in the box substation, especially compact box substation.
2.Service Environmental Condition
Altitude: .< lOOOm
Ambient temperature: -25aC ~ +400C
Relative humidity: The daily average value is not more than 95% and the monthly mean value is not more than 90%.
The surrounding air shall not be polluted by corrosive gas and flammable gas as well as water vapor and so on obviously.
. No location of recurrent strenuous vibration
3.Main structure of switch cabinet
It consists of such parts as bus compartment, 3-position load switch compartment (or circuit breaker compartment), cable compartment, actuator, interlocking mechanism and low-voltage control room as well as measuring circuit or metering circuit and so on. Every compartment is separated by the steel plate so that the fault part avoids affecting the adjacent compartment. It conforms to the GB3906 and IEC298 standard and so on.
. Bus compartment
The bus compartment is arranged on the upper part of cabinet body. The main buses are connected together in the bus compartment and they passes through the whole array of switch cabinet. The arrangement of bus is horizontal and it can be spread out conveniently.
. Load switch compartment
There is a 3-position load switch installed in the switch compartment. The casing of load switch is poured by the epoxy resin. The Sf6 gas is refilled as the arc-extinguishing and insulating medium in the compartment. There are 2 transparent plastic end cover by means of thermal forming installed at the leading end of operating shaft. The contact state can be observed through it. The SF6 gas density gauge or gas density apparatus with alarm contact is installed in the switch compartment according to the client requirement.
. Cable compartment
The cable compartment is mainly used for cable connection. For the connection of single-core cable, the simplest non-shielded cable head is used. At same time, there are such elements as lightning arrester, current transformer and lower grounding switch and so on also can be contained in the enough room. There are observation window and safety interlocking device in the cabinet door as per the standard design. The back plate in the cable compartment is equipped with the sealing cover and appropriate size of cable clamp with support. The frame in front of door at the back plate in the cable compartment can be dismounted for easy cable installation.
. Operating mechanism , interlocking mechanism and low-voltage control room
The low-voltage room with interlocking functions as the screen control at same time. The low-voltage room is equipped with the spring actuator with position indicator and mechanical interlocking device. The auxiliary contact, tripping coil, emergency tripping mechanism, capacitor-type charged display device, key lock and electrical operation device are installed in the low-voltage room. At same time, the control circuit and metering instrument as well as protection relay also can be installed in the spacing of low-voltage room.
There are 2 same low-voltage rooms installed in the 750mm wide cabinet and more accessories can be installed in this size of cabinet.
4.The main technical parameters
NO. | Item | Unit | Technical parameters | ||||
XGN15-12(F) | XGN15-12(F,R) | ||||||
1 | Rated voltage | KV | 12 | ||||
2 | Rated Frequency | Hz | 50 | ||||
3 | Rated insulation level | 1 min power frequency withstand voltage | Kv | To-Grounding and phase -to-phase42;Isolating distance48 | |||
Lighting impulse withstand voltage(peak) | kv | To-Ground and phase-to-phase 75; Isolating distance85 | |||||
4 | Rated current of main bus | A | 630 | ||||
6 | Rated current | A | 630 | 125 | |||
7 | Rated closed loop breaking current | A | 630 | ||||
8 | Rated charging breaking current | A | 10 | ||||
9 | Rated transfer current | A | 1700 | ||||
10 | Breaking no-load transformer capacity | KVA | 1600 | ||||
11 | Rated making current(peak) | KA | 63 | ||||
12 | Rated short-time withstand current | KA | 25 | ||||
13 | Rated peak withstand current | KA | 63 | ||||
14 | Rated short-circuit breaking current | KA | |||||
15 | Peak withstand current of ground circuit(prospective) | KA | 63 | 31.3(Prospective) | |||
16 | Short-time withstand current of grounding circuit | KA | 25 | ||||
17 | Fuse model | SLAJ | |||||
18 | Rated voltage of auxiliary circuit | V | DC220 110 AC220 110 | ||||
19 | IP Code | IP3X | |||||
20 | Mechanical life | Load switch (times) | Times | 5000 | |||
Earthing switch(times) | Times | 2000 |
5.Ring main unit configuration table
Name | Description | Unit | |
Load break switch | FL+C2:D7+C2:D12N36- 24/630-20 | Load break switch for Two positions, no earthing with Gas-pressure meter | Set |
FL(R)N36- 12D/630-20 | Load break switch for Three positions with Gas-pressure meter | Set | |
FLN36- 24/630-20 | Load break switch for Two positions, no earthing with Gas-pressure meter | Set | |
FL(R)N36- 24D/630-20 | Load break switch for Three positions with Gas-pressure meter | Set | |
FL(R)N36- 35/630-20 | Load break switch for Two positions, no earthing with Gas-pressure meter | Set | |
FL(R)N36- 35D/630-20 | Load break switch for Three positions with Gas-pressure meter | Set | |
Operating mechanism | Organization for in line | Manual operation for K type(No button) (not suitable for fuses) | Set |
Organization for in and out line | Manual operation for A type(with button) | Set | |
Organization for in and out line | Electric operation AC220V | Set | |
Organization for in line | Manual for closing and electric for Opening | Set | |
Only for 12kv 24kv (outgoing line) 35kv load break switch is protected by microcomputer | Fuse holders | Top and bottom fuse holder 6pcs totally | Set |
Fuse | (See the below) | Set | |
Interlock system | Down door interlock | The interlock for down door | Set |
Trip device(Including the trip system and trip interlock,work together with fuse holders) | Trip system | Set | |
Trip interlock | Set | ||
Earthing interlock | 500 #/375# earthing components | Set | |
Sensors | 3pcs as one set | Set | |
Voltage Indicator | L-6 | Set |
The general selection principle of rated current of the fuse element selected by transformer capacity is shown in table
Transformer capacity (kVA) | 100 | 125 | 160 | 200 | 250 | 300 315 | 400 | 500 | 630 | 750 800 | 1000 | 1250 | |
Rated current of fuse element (A) | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 |
6. According to the actual use, the SF6 RMU (SM6) cabinet has the following devices.
SF6 (SM6) Switchgear cabinet types | ||||||||||
NO. | Name | Specification | Unit | Qty | NO. | Name | Specification | Unit | Qty | |
XGN15-12 Lifttlig Switchgear | Set | 1 | XGN15-12 Outline Switchgear | Set | 1 | |||||
1 | Lighting Arrester | HY5WS 17/50 | Set | 1 | 1 | SF6 load break swith | FRLN36-12D/125-31.5 | Set | 1 | |
2 | Voltage display | L-6 | Set | 1 | 2 | Operating mechanism | Manual for closing and Electric for Open | |||
3 | Electromagnetic lock | DSN-Y | Set | 1 | 3 | Gas meter | Set | 1 | ||
4 | Sheet metal | 375*916*1635 | Set | 1 | 4 | Outline Electromagnetic lock | 375# | Set | 1 | |
5 | Lighting Arrester | HY5WS 17/50 | Set | 1 | ||||||
NO. | Name | Specification | Unit | Qty | 6 | Sensor | CG5-10 140mm | Set | 1 | |
XGN15-12 Mertering Switchgear | Set | 1 | 7 | Voltage display | L-6 | Set | 1 | |||
1 | Sensor | CG5-10 140mm | Set | 1 | 8 | Fuse | 10A-63A | Set | 1 | |
2 | Voltage display | DXN-Q | Set | 1 | 9 | Sheet metal | 375*1000*1635 | Set | 1 | |
3 | Electromagnetic lock | DSN-Z 220V | Set | 1 | ||||||
4 | Sheet metal | 750*916*1635 | Set | 1 | NO. | Name | Specification | Unit | Qty | |
XGN15-12 Outline Switchgear | Set | 1 | ||||||||
NO. | Name | Specification | Unit | Qty | 1 | SF6 load break swith | FRLN36-12D/125-31.5 | Set | 1 | |
XGN15-12 Inline Switchgear | Set | 1 | 2 | Operating mechanism | Electric AC2200 | Set | 1 | |||
1 | SF6 load break swith | FLN36-12/620-20 | Set | 1 | 3 | Gas meter | Set | 1 | ||
2 | Operating mechanism | Manual A type | Set | 1 | 4 | Outline Electromagnetic lock | 375# | Set | 1 | |
3 | Gas meter | Set | 1 | 5 | Lighting Arrester | HY5WS 17/50 | Set | 1 | ||
4 | Interlock for up and down door | Set | 1 | 6 | Sensor | CG5-10 140mm | Set | 1 | ||
5 | Lighting Arrester | HY5WS 17/50 | Set | 1 | 7 | Voltage display | L-6 | Set | 1 | |
6 | Sensor | CG5-10 140mm | Set | 1 | 8 | Fuse | 10A-63A | Set | 1 | |
7 | Voltage display | DXN-Q | Set | 1 | 9 | Sheet metal | 375*1000*1635 | Set | 1 | |
8 | Electromagnetic lock | DSN-Z 220V | Set | 1 | ||||||
9 | Sheet metal | 375*916*1635 | Set | 1 | NO. | Name | Specification | Unit | Qty | |
XGN15-12 Inline VCB switchgear | Set | 1 | ||||||||
NO. | Name | Specification | Unit | Qty | 1 | VCB | VS1-12/630A-25KA | Set | 1 | |
XGN15-12 Inline Switchgear | Set | 1 | 2 | Disconecting switch | GN30-12/630-25KA | Set | 1 | |||
1 | SF6 load break swith | FLN36-12/620-20 | Set | 1 | 3 | Metal plate mechanism | Set | 1 | ||
2 | Operating mechanism | Electric AC2200 | Set | 1 | 4 | Lighting Arrester | HY5WS 17/50 | Set | 1 | |
3 | Gas meter | Set | 1 | 5 | Sensor | CG5-10 140mm | Set | 1 | ||
4 | Interlock for up and down door | Set | 1 | 6 | Voltage display | DXN-Q | Set | 1 | ||
5 | Lighting Arrester | HY5WS 17/50 | Set | 1 | 7 | Electromagnetic lock | DSN-Z 220V | Set | 1 | |
6 | Sensor | CG5-10 140mm | Set | 1 | 8 | Sheet metal | 750*916*1885 | Set | 1 | |
7 | Voltage display | DXN-Q | Set | 1 | ||||||
8 | Electromagnetic lock | DSN-Z 220V | Set | 1 | NO. | Name | Specification | Unit | Qty | |
9 | Sheet metal | 375*916*1635 | Set | 1 | XGN17-12 Outline VCB switchgear | Set | 1 | |||
1 | VCB | VS1-24/630A-25KA | Set | 1 | ||||||
NO. | Name | Specification | Unit | Qty | 2 | Disconecting switch | GN30-10/630-25KA | Set | 1 | |
XGN15-12 Outline Switchgear | Set | 1 | 3 | Metal plate mechanism | Set | 1 | ||||
1 | SF6 load break swith | FRLN36-12D/125-31.5 | Set | 1 | 4 | Lighting Arrester | HY5WS 17/50 | Set | 1 | |
2 | Operating mechanism | Manual A type | Set | 1 | 5 | Sensor | CG5-10 140mm | Set | 1 | |
3 | Gas meter | Set | 1 | 6 | Voltage display | DXN-T | Set | 1 | ||
4 | Outline Electromagnetic lock | 375# | Set | 1 | 7 | Sheet metal | 1000*1210*2300 | Set | 1 | |
5 | Lighting Arrester | HY5WS 17/50 | Set | 1 | 8 | Grounding knife | JN15-12 | Set | 1 | |
6 | Sensor | CG5-10 140mm | Set | 1 | ||||||
7 | Voltage display | L-6 | Set | 1 | Note; | This price without Copper bar,without current transformer,without seal plate. | ||||
8 | Fuse | 10A-63A | Set | 1 | extra add 20 usd ,if the Sheet metal need higher one floor or wider one floor | |||||
9 | Sheet metal | 375*1000*1635 | Set | 1 |