Rpm100 Quality Good Price Power Multimeter图1Rpm100 Quality Good Price Power Multimeter图2Rpm100 Quality Good Price Power Multimeter图3Rpm100 Quality Good Price Power Multimeter图4Rpm100 Quality Good Price Power Multimeter图5Rpm100 Quality Good Price Power Multimeter图6

Rpm100 Quality Good Price Power Multimeter

Price $536.00
Min Order 1 Piece  
Shipping from Guangdong, China
Quantity
-+
Product details
RPM100
2 Years
2 Years
Digital
Direct Connected
Multi-Functional Energy Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Maximum Demand Meter, Power Quality Analyser
Single-Phase, Two-Phase, Three-Phase
Electronic Meter
Terminal
Continuous Wave
Power Meter
RoHS, ISO, CE
Customized
10va Max
85~265 VAC 50/60Hz (Depend on Order)
5 Current Input: 0.05-5.5A
4 Voltage Input : Max 690VAC (L-L)
RS485 Port of Modbus RTU
Ethernet Port of Modbus TCP/IP+Web Server
Romaz
Carton Box
96*96
China
9030390000
Product Description

Product Description


Measurements
Measurements:VL-L, VL-N, I, In, Iz, Cos , Pf, Hz, W, ∑W, Va, ∑Va, Var, ∑Var, Kwh, Kvarh, V-THD, I-THD, 1-128th harmonic ,
   system running hours,% voltage unbalance, % system load,% system leakage,frequency;Fast simultaneous sampling on all
8 channels at 1024 samples/cycle(True RMS measurements)
For single-phase, two-phase, three-phase system
4 voltage channel input, voltage direct connection up to 690VLL or through PT for MV and HV systems.
5 current input: 0.05-5.5A
4th current channel dedicated for neutral current measurements, the current measuring range (CT primary and secondary )
   
 can be programmed together with the main three-phase channels
5th current channel reserved for Earth Leackage monitoring (ZCT input) according to IEC60755 & IEC61140
Suitable for 45-65Hz systems
All measured voltage characteristics certified according to IEC/EN61000-4-30:2015 Ed.3, Class A
4 quadrants energy measurement 
Transients detection >25us, Detection of events >10ms
Voltage flicker measurement, and waveform capture
Maximum, minimum and demand for U, I, P, Q, S in hours, days, months
Phase diagram for voltage, current Detects CT wiring errors 

Data storage & recordings
Voltage and current sag/swell and transient event capture
Waveform acquisition and capture of voltage and current
Automatic fault analysis and report: Phase sequence, Phase fault, Voltage over, Voltage under, Sag/swell, Frequency over,
   Current over, Short circuit, Leakage,Voltage harmonic, Current harmonic(according to IEC62606: 2013)
Alarm event log: VL-L, VL-N, I, In, ΣW, ΣVar, THD-U, THD-I...
Monthly electricity statistics
Built in 256M flash memory &32MB RAM for event and transient memory
Micro SD(support 32GB) for fault logger and data logger
Data recorded in standard excel file formats for further EN50160 analysis

Clock & language
Real time clock with integrated backup rechargeable battery
English, Chinese (traditional & simplied) or other

Communication
RS485 port of Modbus RTU
Ethernet port of Modbus TCP/IP+web server

Function module (only one can be selected)
7 digital input+2 analog output (4-20mA) for V1, V2, V3, V12, V23, V31, I1, I2, I3
Ethernet (Modbus TCP), web server+2 digital input+2 relay output (remote or alarm)
LoRa wireless (Private protocol)+2 digital input+2 relay output (remote or alarm)
RS-485 interface (Modbus RTU)+2 digital input+2 relay output (remote or alarm)
WIFI wireless+2 digital input+2 relay output (remote or alarm)

Product Parameters

Auxiliary Supply
Operating voltage (Un)85···265 VAC 50/60Hz 10W / 100-285VDC/24-48VDC(depend on order)
Power consumption10VA max
Measurement input
Voltage inputs for direct connection:Phase-neutral(L-N): max 400V RMS CAT III
Input impedance(for direct voltage inputs):>4MΩ
CT inputs:max 5.5A RMS
CT inputs overload capacity:max 10A
CT inputs Self-consumption :<0.2VA
Accuracy
Three phase voltage:± 0.2%
Currents:± 0.2%
Powers:± 0.3%
Powers factor:± 0.3%
Frequency:± 0.02%
Harmonics:Class 1 (IEC/EN61000-4-7)
Active energy:Class 0.2S (IEC/EN 62053-22)
Reactive energy:Class 0.5S (IEC/EN 62053-23)
Insulation
Insulation voltage
3kV for 1 min., 50Hz
Display
Display type
3.2inch 240x160 pix LCD
I/O
Digital inputs:
Active dry contact
Digital outputs:
2 Relay N/O 220VAC 5A
Analog outputs:
4-20mADC / max load 500Ω
Pulse output:
12-30VDC Max.50mA, Min. 50msec pulse width
Memory 
Recording memory:
max 32 GB SD (TF)
Communication
Ethernet port:
Auto MDIX Rj45 10/100 Base Ethernet
RS-485 port:
1 optoisolated, 4800-57600
Protocols:
HTTP, HTTPS, Modbus RTU/TCP
Environmental conditions
Opterating temperature:
-10···+55°C
Storage temperature:
-25···+75°C
Relative humidity:
95% max without condensing
Altitude:
max 2000m AMSL
Installation & use:
Internal
Mechanical characteristics
Mounting:
Panel mount 96x96mm(The panel cut-size 92*92mm)
Size:
Front(WXH)96x96mm, Rear (HxD) 90x70mm
Degree of protection:
IP40(optional IP54) on front, IP20 housing and terminals
Weight:
400g
Standard compliance
reference standard:
IEC61010-1; IEC61557-1;IEC61557-12; IEC61326-1;IEC62053-21;
IEC62053-22; IEC62053-31; IEC60068-2-1; IEC60068-2-30;
IEC60364-5-52; IEC61000-3-2; IEC61000-3-3; IEC61000-4-2;
IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6;
IEC61000-4-8; IEC61000-4-11; IEC61000-4-30