RM120-600
Three Phase
On-line
Overcurrent
Industry
Lighting/Power
Long-acting Machine
Sine Wave Output UPS
Large Type
Centralized Model
Kemapower
KEMAPOWER
Safety Packing
Modular UPS
China
8504403090
Product Description
RM60 3PH Rack Module UPS
KEY FEATURES
- Power Module 60K Rack Module UPS 120K/180K/240K/300K/480K/600K
- High effciency over 94.5% at 50% load, Output Power Factor 1 technology
- DSP control, ,online double conversion,Integrated modular and parallel technology
- High scalability,Single rack expanding 120KVA to 600KVA, N+1 or N+X redundancy in the same rack, supports 1+1 cabinet parallel operation.
- Built-in maintenance bypass, praevia all panel control and connectors
- Highly reliable operation with redundant power supply in STS
- High overload Capacity , 60mins@110%, 10Mins@125% ,1mins@150%
- 32 to 40PCS adjustable Battery numbers
- Adiustable charging current,Max 18A
TECHNICAL SPECIFICATIONS
| MODEL | RM120/60X30U-RYY | RM180/60X30U-RYY | RM240/60X-RYY | RM300/60X-RYY | RM480/60X42U-RYY | RM600/60X42U-RYY |
| PHASE | 3-phase in/3-phase out | |||||
| CABINET CAPACITY* | 120KW | 180KW | 240KW | 300KW | 480KW | 600KW |
| BATTERY TYPE | External Battery | |||||
| One Power Module Capacity | 60KVA/60KW | |||||
| Max. Power Module No. | 2 | 3 | 4 | 5 | 8 | 10 |
| INPUT | ||||||
| Nominal Voltage | 380VAC/400VAC/415VAC (3Ph+N) | |||||
| Voltage Range | 305 ~ 478 VAC at 70% - 100% load; 208 ~ 478VAC for <70% load | |||||
| Nominal Frequency | 50/60Hz (Auto sensing) | |||||
| Frequency Range | 40Hz ~70Hz | |||||
| Power Factor | > 0.99 at 100% load, >0.98 at 50% load | |||||
| Harmonic Distortion (THDi) | < 3% @ 100% load | |||||
| OUTPUT | ||||||
| Nominal Voltage | 380VAC/400VAC/415VAC (3Ph+N) | |||||
| Voltage Regulation (Steady State) | <=± 1% Typical (balanced load) <=± 2% Typical (unbalanced load) | |||||
| Nominal Frequency | 50/60Hz | |||||
| Frequency Range (Synchronized Range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||
| Overload Capability | 110% for 1 hour, 125% for 10 mins , 150% for 1 min and 200ms for >150% | |||||
| Harmonic Distortion | <= 2% THD (Linear Load) <= 4% THD (Non-linear Load) | |||||
| Efficiency | Up to 96% | |||||
| BATTERY / CHARGER | ||||||
| Nominal Voltage | +/- 192V~+/- 240V (Selectable) | |||||
| Maximum Voltage | +/- 240V (12V x 40 Pcs) | |||||
| Minimum Voltage | +/- 192V (12V x 32 Pcs) | |||||
| Floating Charge Voltage | 2.28V/Cell (2.25~2.33 Selectable) | |||||
| Boost Charging Voltage | 2.35V/Cell | |||||
| Temperature Compensation | Yes | |||||
| Maximum Charging Current (Per Power Module) | 18A | |||||
| PHYSICAL | ||||||
| Cabinet Dimension (D x W x H) mm | 1100 x 600 x 1475 | 1100 x 600 x 2010 | 1065 x 1000 x 2000 | |||
| Net Weight (kgs) | 308 | 352 | 516 | 516 | 932 | 1020 |
| ENVIRONMENT | ||||||
| Operation Temperature | 0 ~ 40ºC | |||||
| Relative Humidity | 0 ~ 95% non-condensing | |||||
| Altitude* | <1000m for Nominal power | |||||
| IP Class | IP 20 | |||||
| MANAGEMENT | ||||||
| RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7, Linux and MAC | |||||
| Optional SNMP | Power management from SNMP manager and web browser | |||||
| STANDARDS | ||||||
| Safety | IEC/EN 60950-1; IEC/EN 62040-1 | |||||
| EMC | IEC/EN 62040-2 Category C3 | |||||
*If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
| Model | Description | Dimension DxWxH(mm) | Weight (kg) | ||
| PM-60 | 3P/3P 60KVA60KW power module | 750 x 438 x 133 (3U) | 44 | ||
PRODUCT DISPLAY