APV400
Piezoelectric
13.5 to 28V DC
New
IP66
Aluminium/Stainless Steel
4 to 20 Ma (with Hart Option)
455 Omega (Without Hart); 495 Omega (with Hart)
Linear 10 to 130 mm; Rotory 30° to 100°
Linear/Equal Percentage/Inverse Equal Percentage/
4 to 20 Ma (Option)
-30 to 80 ºC (-40ºC Option)
Thread
1.5 to 8.0 Bar
1/4 NPT or RC1/4
Exia Iic T4 … T6 Ga, Exdb Iic T4 … T6 GB
HollySys
Carton Box
China
7318190000
Product Description
APV400 Intelligent Valve Positioner operates on the principle of piezoelectric valves and is equipped with HART communication protocol. It effectively converts a 2-wire 4 to 20 mA control signal into pneumatic output for the actuator, making it suitable for both pneumatic linear actuators and rotary actuators. This functionality enables precise positioning of the valve according to predetermined settings. The positioner features a compact and modular design that offers high cost-effectiveness. Its self-tuning capability for control parameters, combined with excellent adaptability, significantly reduces setup time while ensur ing optimal control performance.
Features
· Adaptive predictive control algorithm for faster response and more precise control.
· Automatic detection of valve lower and upper limits, opti mizing valve control parameters to enhance accuracy.
· Dot matrix LCD display with multi-language support, ro tatable by 180° for easy observation. Equipped with four configuration buttons for local valve control and settings adjustments.
· Supporting parameter configuration for split range, characteristic curves, stroke range and direction, tight closure, dead zone, control parameters, digital input, alarm and fault outputs, and more.
· Diagnostic capabilities include leakage detection, partial stroke testing, upper and lower limit monitoring, pressure and temperature diagnostics, stroke accumulation, directional change counts, and piezoelectric operation monitoring.
· IDM software allows setup and calibration of valve accessories, with status monitoring and alarm tracking.
· Compatible with HART 5 and HART 7 communica tion protocols.
· Including one isolated digital input and two dry con tact inputs.
· Digital output with electric isolation provides alarm or fault notifications.
· Electrically isolated position feedback block outputs 4 to 20mA position feedback.
· Optional "faillast" function ensures operational stability during power, gas, or signal failure.
· Equipped with surge protection for enhanced reliability.
Main Parameters
Model Code
Certifications
Product Images

Packaging & Delivery
Related Products
A100 Globe Control Valve

A400 Ball Valve

A700Butterfly Valve
Company Profile



Features
· Adaptive predictive control algorithm for faster response and more precise control.
· Automatic detection of valve lower and upper limits, opti mizing valve control parameters to enhance accuracy.
· Dot matrix LCD display with multi-language support, ro tatable by 180° for easy observation. Equipped with four configuration buttons for local valve control and settings adjustments.
· Supporting parameter configuration for split range, characteristic curves, stroke range and direction, tight closure, dead zone, control parameters, digital input, alarm and fault outputs, and more.
· Diagnostic capabilities include leakage detection, partial stroke testing, upper and lower limit monitoring, pressure and temperature diagnostics, stroke accumulation, directional change counts, and piezoelectric operation monitoring.
· IDM software allows setup and calibration of valve accessories, with status monitoring and alarm tracking.
· Compatible with HART 5 and HART 7 communica tion protocols.
· Including one isolated digital input and two dry con tact inputs.
· Digital output with electric isolation provides alarm or fault notifications.
· Electrically isolated position feedback block outputs 4 to 20mA position feedback.
· Optional "faillast" function ensures operational stability during power, gas, or signal failure.
· Equipped with surge protection for enhanced reliability.
Main Parameters
· Main Parameters
· Type: Piezoelectric
· Signal: Two-wire 4 to 20 mA DC input, optional HART 5 and HART 7, 4 to 20 mA feedback output
· Protection Grade: IP66
· Explosion-proof: Exia IIC T4 … T6 Ga, Exdb IIC T4 … T6 Gb
· Three-break Fail Last: Optional valve manifolds can make valve fail last in case of power failure, gas failure, and signal failure
· Surge: Surge protection function
· Diagnostic Function: Leakage detection, partial stroke test, upper limit and lower limit monitoring, pressure detection diagnos tic, temperature diagnostic, stroke accumulation, direction change times, piezoelectric operation times, etc.
· Type: Piezoelectric
· Signal: Two-wire 4 to 20 mA DC input, optional HART 5 and HART 7, 4 to 20 mA feedback output
· Protection Grade: IP66
· Explosion-proof: Exia IIC T4 … T6 Ga, Exdb IIC T4 … T6 Gb
· Three-break Fail Last: Optional valve manifolds can make valve fail last in case of power failure, gas failure, and signal failure
· Surge: Surge protection function
· Diagnostic Function: Leakage detection, partial stroke test, upper limit and lower limit monitoring, pressure detection diagnos tic, temperature diagnostic, stroke accumulation, direction change times, piezoelectric operation times, etc.
Model Code
Model Type | Code | Description |
APV400 | ||
Stroke type | L | Linear |
R | Rotary | |
Action type | S | Single acting |
D | Double acting | |
Explosion protection | n | Non-explosion (IP66) |
i | Intrinsically safe (Exi) | |
d | Flameproof (Exd) | |
t | Dust ignition-proof (Ext) | |
k | Intrinsically safe (Exi), dust ignition-proof (Ext) | |
e | Flameproof (Exd), dust ignition-proof (Ext) | |
Feedback lever | 1 | 10 to 30 mm |
2 | 40 to 130 mm | |
X | User-defined | |
8 | 0 to 90° | |
Feedback module | 0 | None |
1 | Position feedback 4 to 20 mA | |
2 | Limit switch | |
3 | Position feedback 4 to 20 mA + limit switch | |
Communication function | 0 | None |
H | HART | |
Electrical connection | M | M20 × 1.5 female |
N | 1/2 NPT female | |
Air supply connection | 1 | 1/4 NPT female |
Fail position | R | Fail safe |
H | Fail last (selected if three-break fail last is required) | |
G | Fail open | |
Ambient Temperature | T | -30 to 80ºC |
L | -40 to 80ºC | |
Housing material | A | Die-cast aluminum type A (for intrinsically safe, normal type) |
B | Die-cast aluminum type B (for Exd) | |
C | Stainless steel type C (for intrinsically safe, normal type) | |
D | Stainless steel type D (for Exd) | |
Pressure gauge | 0 | None |
1 | Stainless steel pressure gauge | |
Mounting bracket | 0 | None |
1 | With rotary stroke mounting bracket (assembled to actuator 30 × 80 × 42) | |
2 | With linear stroke mounting bracket (assembled to actuator 30 × 130 × 52) | |
X | Customized bracket | |
Options | 0 | None |
A | Split-range control | |
B | Alarm module/digital I/O module (DIO) | |
C | Pressure measurement module |
Certifications
NEPSI | NEPSI intrinsically safe Ex ia IIC T4 … T6 Ga Applicable standard: GB/T 3836.1-2021, GB/T 3836.4-2021 |
NEPSI explosive-proof Ex db IIC T4 … T6 Gb Applicable standard: GB/T 3836.1-2021, GB/T 3836.2-2021, GB/T 3836.31-2021 | |
NEPSI dust explosion prevention Ex tb IIIC T85ºC … T135ºC Db Applicable standard: GB/T 3836.1-2021, GB/T 3836.2-2021, GB/T 3836.31-2021 | |
CCC | China Compulsory Product Certification, NEPSI Ex ia IIC T4 … T6 Ga/Ex db IIC T4…T6 Gb/ Ex tb IIIC T85ºC …T135ºC Db |
Others | Industrial automation instrument intelligent evaluation certificate Applicable standard: T/SHIIA000001-2020 |
Product Images


Packaging & Delivery
Category | Product Size | Gross Weight | International Commercial Terms (Incoterms) | Terms of Payment | Nearest Port |
APV400 Valve Positioner | 208 mm × 98 mm × 104 mm (excluding drive shaft attachment, blocking parts, manometer module) | About 2.0 kg | CIF, CFR, DAP | LC, T/T, D/P | Shanghai, Guangzhou,Tianjin |
Related Products
A100 Globe Control Valve


A400 Ball Valve


A700Butterfly Valve