HMZH-5
Life Long Support
1
Sf6 Gas Analyzer
Digital
Manual Control
15
AC220V
Dew Point
Purity Point
S02
Co
H2s
Humidity
Temperature
Siemens and Other Brand
12 Copper Fittings
HMDQ
Plywoodencase
Made in China
9030390000
Product Description
Comprehensive sf6 gas analyzer for purity, dew point test
Brief Introduction
SF6 comprehensive analyzer is specially used for index detection of insulating gas in SF6 electrical equipment, and adopts the high-performance sensor for measurement of dew point, purity and decomposition product to guarantee the accurate and stable test results. Equipped with the unique gas circuit structure, it adopts the high-precision electronic flowmeter for full-automatic detection so that the SF6 can be more accurate in gas analysis. Three indexes can be detected via one-time measurement, which greatly reduces the workload of users and improves the work efficiency


Feature

Parameter
SF6 purity detection module
SF6 humidity detection module
Flow regulation 1: 0.2L/min; Flow regulation: 2:0.5-0.6L/min
Parameters of whole machine





Brief Introduction
SF6 comprehensive analyzer is specially used for index detection of insulating gas in SF6 electrical equipment, and adopts the high-performance sensor for measurement of dew point, purity and decomposition product to guarantee the accurate and stable test results. Equipped with the unique gas circuit structure, it adopts the high-precision electronic flowmeter for full-automatic detection so that the SF6 can be more accurate in gas analysis. Three indexes can be detected via one-time measurement, which greatly reduces the workload of users and improves the work efficiency


Feature
- Dual-channel flow control design without fear of pressure fluctuation
- Utilization þf high-precision electronic flowmeter, with flow overruns prompt
- Switch of trends of measuring objects, and real-time display of data
- .Self-calibration function of zero and slope after startup
- Crossing-resistance interference technology of sensor
- Cleaning of residual gas in air circuit
- Lithium battery with ultra-large capacity, and dual purpose of AC / DC
- Large-capacity data storage, and USDB one-key data export
- Thermosensitive mute printer for rapid printing on the scene

Parameter
SF6 gas decomposition product detection module
Measurement scope | [SO2]0~100 µl/l, [H2S]0~100 µl/l, [CO]0~1000 µl/l |
Precision | SO2, H2S: ±0.5µl/l if measurement value ≤10 µl/l; ±5% if measurement value >10 µl/l CO: ±2.0 if measurement value ≤50 µl/l ±4% if measurement value >50 µl/l |
Repeatability | SO2, H2S: ±0.2 µl/l if measurement value ≤10 µl/l; ±2% if measurement value >10 µl/l CO: ±1.5 µl/l if measurement value ≤50 µl/l; ±3% if measurement value >50 µl/l |
Resolution | SO2, H2S, CO: 0.1 µl/l |
Response time | ≤30s |
Measurement scope | 0~100% |
Precision | ≤±0.5% (90~100%:≤±0.2%) |
Repeatability | ≤±0.2% |
Resolution | 0.01% |
Response time | ≤30S |
Dew point range | ―80ºC~+20ºC |
Measurement accuracy | ±0.5ºC |
Micro-water scope | 0.05~23100 μL/L |
Measurement response time (+20ºC) | -60ºC →20ºC 5S[10s] 20 ºC→-60ºC 10S[300S] |
Resolution | Dew point: 0.1ºC Micro-water: 0.1ppm (100ppm~1000ppm) 0.01ppm(10ppm~100ppm) |
Repetition: | ±0.2ºC |
Parameters of whole machine
Charging source | 220VAC±10% 50HZ |
Battery | Lithium battery 12V 17.5AH |
Service time | >10h |
Display screen | 7-inch color touch screen |
Sample gas pressure | ≤1.0Mpa |
Size | 467×372×177mm |
Weight | About 8.5kg |