MCM263T Multi-channel energy meter provides a compact and robust metering solution; it can enable reliable monitoring of commercial building electrical or industry loads with a low installation cost-per-point by combining sub-metering.
The branch circuit power meter performs real-time metering, measures energy consumption and generation, multi-tariff time-of-use (TOU), and monitors power quality for advanced communications options, including Modbus via RS485 and Ethernet interface. Various combination options of I/O communications provide for extensive reliable data exchange.
Max 18-channel circuits for single-phase circuits(MCM261T) or 6 channels for three-phase circuits (MCM263T). Multiple units can be connected to meter unlimited number of circuits.
The versatility of MCM263T multi-channel power meters is ideal for multi-tenant or departmental metering applications within office towers, condominiums, apartment buildings, shopping centers, and other multi-user environments
* Accuracy class 0.5
* Current measuring .../5 or .../1 A
* 6'' dot matrix LCD screen
* Universal series power supply (85-265VAC/DC)
* With RS-485 Modbus/RTU Communications
* Optional 6 channels Digital Input (DI) and 2 channels Digital Output (DO)
* Optional advanced electrical parameter*
* Optional record and read tariffs ratio, up to 3 months (TOU record)
* Optional max 99 lists SOE record
* Accept customization design

Working Power
AC/DC 90-240V, 45-65Hz, or DC 20-60V (Optional)
Maximum power consumption 6W
Input
Current: | Rated 5A (Optional 1A) |
Voltage: | Rated 0~480V (CATIII-300V) |
Frequency: | 45-65Hz |
Current overload : | 1.2 times rated continuous; 5 seconds for 10 times of the rated |
Voltage overload : | 30 seconds for 2 times of the rated |
Accuracy Standard
Parameter | Accuracy | A phase | B phase | C phase | All |
Voltage Current Active Power Reactive Power Apparent power Power Factor Active Energy Reactive Energy Frequency | 0.2 0.2 0.5 0.5 0.5 0.5 1 2 0.1 | V1 A1 W1 var1 VA1 PF1 | V2 A2 W2 var2 VA2 PF2 | V3 A3 W3 var3 VA3 PF3 | W var VA PF Wh varh Hz |
EMC Test
Parameter | Standard | Test voltage |
Discharge immunity test | IEC61000-4-2 level 4 | 8kV |
Surge (Shock) immunity test | IEC61000-4-5 level 4 | Common test voltage 4kV |
Fast transient burst immunity test | IEC61000-4-4 level 3 | Input 1kV; Power supply 2kV |
Reference Standard
Basic Electricity | IEC 61557-12:2018 |
Active energy | IEC 62053-21:2020 |
Reactive energy | IEC 62053-23:2020 |
IEC/EN 61010-1:2012
2kV AC RMS 1 minute, between input/output/case/power supply
Work Environment
Temperature: -20C~ +60C
Humidity: RH 20%~95% (No condensation)
Storage Environment
Temperature: -25C~+70C
Humidity: RH 20%~95%
Installation
35mm Din-Rail
Dimension
L × H × D =108*110*66mm

The common application of MCM series multi-channel energy meters is in the following:
- Manufacturing plants, industrial parks and processing workshops; Office buildings, commercial centers and shopping malls;
- Residential communities, apartment buildings and single-family homes;
- Schools, hospitals and government buildings;
- Transportation infrastructure, airports, train stations and subway stations;
- Data centers such as server rooms, network operation centers.


Exhibition photo display