Specifiation data of 11kV composite insulator
Type | Rated voltage (kV) | Rated mechanical tension load (kN) | Structure height (mm) | Min nominal creepage distance (mm) | 1min power frequency wet withstand voltage (kV) | Full wave lightning impulse withstand voltage peak value (kV) |
FXBW6-11/70CT | 11 | 70 | 380 | 480 | 45 | 115 |
Materials of 11kV composite insulator advantage
1). Prototype Tested and 5000hours aging tested.
2). Warranty: 15 Years guarantee for 11kV composite insulator after ETD.
3). 18 Years manufacturing and exporting experience with 11kV composite insulator.
4). ISO9001 and ISO14001 and OHSAS18001 quality management.